Chlorine gas leak detector M 4510 C

  • Simultaneous 2 point measurement 
  • 6 relay outputs
  • Fault indication
  • Easy to install
  • Manual  test for alarm indicators

GENERAL

The M 4510 C series Controlmatik ABW chlorine gas leak detector unit is assembled as separate signal evaluation unit with display, unit with two adjustable alarms and fault alarm, power supply unit and separate detection cell - probe.

Chlorine detection cell is mounted in an IP 65 housing and features 4- 20 mA output  which is connected to the signal evaluation unit. Two adjustable alarms can be set and  following units can be activated in case of chlorine gas leak:

  • alarm horn
  • flashing light
  • ventilation system 
  • neutralisation system

For detection cell see product information for Chlorine gas detection sensor M 2103 C.

Contact us for more info

Chlorine gas leak detector unit ( M 4510 C):

Measuring unit:  PPM

Temperature range: from - 10 to + 50 °C

Resolution at 20 °C: 0,1 PPM

Repeatability: 2%

Measuring range: 0 - 10 PPM or 0 - 20 PPM

Supply voltage: 220V, 50/60Hz

Fuse : 1 A (T)

Analogue output: 2 x 4-20 mA  

Output voltages: 0-10 V DC (on request)

Current input: 2 x 4 - 20 mA for sensor 1 and sensor 2

Consumption: approx.  4 VA

Measuring loop resistance: 740 Ohm

Display: LCD 4 lines, 12 characters

Relay output : 4 relay output; max: 250V/8A

Weight: M 4510: approx. 2.5 kg

M 2103: 0,5 kg

Housing protection type: IP 65

 

Probe unit ( M 2103):

For data see M 2103 chlorine gas detection sensor documentation